Surgex SX-AX20 User Manual Page 2

  • Download
  • Add to my manuals
  • Print
  • Page
    / 3
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 1
Axess Quick Start Guide Page 2
Changing the IP Address
1. Command Line Interface (CLI).
All configuration parameters may be set using the
Command Line Interface (CLI). The CLI is accessed
through the network using a telnet client, or through the
serial port.
Open a telnet client and point it to the current IP
Address of the Axess.
(Factory Default is 192.168.0.254, telnet Port 23)
Connect to the Serial port.
(Factory Default is 115200,8,n,1)
Upon connection, press Enter, and then enter the
username and password when prompted.
The example shows the basic commands to set the
network parameters. After setting these parameters, the
Axess will need to be rebooted for the settings to take
effect. Any command that requires rebooting of the
Axess will provide a prompt to do so. All commands
may be entered as required before rebooting. Once the
IP address is set, the following command can be used to prevent DHCP from altering it:
set ipmode static
2. DHCP
A DHCP server will automatically assign an IP address (dynamic address) as well as
Subnet Mask and Gateway to the Axess.
To enable this feature, configure the Axess with the command set ipmode dhcp
Then reboot the Axess by entering the command reboot
To find the IP address of the Axess, you will need to query your DHCP server and
locate the MAC address of the Axess in the DHCP server’s IP / MAC table. You can
also access the CLI and use the get network command, or use the Discover provision
of the Axess Setup and Control Utility (SCU).
Page view 1